Designed
specifically for cultured marble
manufacturing to conform to national codes
Removes styrene vapors and contains over
spray for a cleaner, safer work place.
Standard sizes or custom configurations for
your specific production needs. Well lighted
interior with smooth walls allow easy
cleaning and maintenance. External flanges
on all wall and roof panels provide strength
and rigidity. All bolted construction for
easy assembly.

MODEL FS149
|
Construction: |
All
bolted assembly, 18 gage
pre-formed galvanized steel
panels with 14 gage pre-formed
galvanized structural stringer
angles and roof support beams
Working area width 14’-0’, depth
9’-0”, interior height 7’-6”,
overall depth 12’-3” |
|
Exhaust Fan: |
30”
dia. tubeaxial fan with
non-sparking, balanced aluminum
blade and 3 HP explosion proof
rated motor, 230 volt – 60 hz –
3 phase. Single phase and 50 hz.
rated power options available.
UL and CSA listed |
|
Lighting: |
Two
4 tube fluorescent fixtures,
hazardous location rated, 120
volt – 60 hz – 1 phase.
Power options include 50 hz
rated ballast and bulbs. UL and
CSA listed |
|
Pneumatic Door: |
Standard, pneumatic operated
up/down door with control valve
permits sprayed mold transfer
directly opening in side wall of
booth into gel cure heat tunnel |
|
Manometer: |
Differential air pressure
indicator gauge indicates filter
efficiency for cleaning or
replacement. Graduated 0” to 3”
water column indicator scale |
|
Filter Media: |
Flame retardant accordion style
filter. UL listed and factory
approved |
|
Filter Efficiency: |
Average capturing
efficiency- 97.14%.
Actual efficiency is
a function of the
viscous material
being sprayed and
the spraying
conditions
Click drawing to
enlarge. |
 |
|
|
Final Assembly: |
Bolted on site field assembly.
Typical installation time is 2-3
persons 10 hours.
Components are shipped crated,
boxed, and palletized with all
hardware required for assembly |
|
Fire Suppression: |
Local codes may require an
automatic fire protection
(sprinkler) system. This system
must be furnished and installer
by a qualified local contractor |
|
Optional: |
|
Custom sizes and configuration
available by request |
|
Exhaust Stack Package, ES3018
includes 1 – 10 ft exhaust stack
30” dia, automatic damper
weather cap, roof flange, rain
skirt, and hardware necessary
for installation |
|
Spray gun activated hanger
switch stops and starts exhaust
fan. Package Includes hanger
bracket, class 1, Groups A,B,C,
and D rated limit switch With
NEMA 4 magnetic starter and
solenoid air valve |
|
|
Conformance: |
Conforms to applicable codes:
NEC: Article 516, Spray
Application, Dipping and Coating
Processes
OSHA: Section 1920.107, Spray
Finishing using Flammable and
Combustible Materials
NFPA: Publication #33, Spray
Applications using Flammable and
Combustible Materials |
|